Subject: Civil Engineering Chapter: Foundation Engineering Topic: 19.7 Pile Foundations

1. Introduction

A pile is a slender, relatively long structural member that is driven, bored or screwed into the ground to transmit the load of a structure through weak surface soil to a stronger stratum or to distribute the load into the soil along its length. Pile foundations are the most common type of deep foundation and are used when the surface soil cannot support the loads, when heavy column loads or concentrated loads must be carried, when uplift or lateral forces act on the structure, when the water table is high, and when bridge piers and abutments must resist scour. For an examination candidate, pile foundations are a rich source of questions on classification, pile capacity estimation, group efficiency, negative skin friction and the factors of safety used in design.

The behaviour of a pile depends on how the load is transferred to the soil. An end-bearing pile rests its tip on a hard stratum such as rock or dense sand and carries most of its load at the tip, while a friction pile develops its capacity from the skin friction along the shaft in soft soil, and a combined pile uses both mechanisms. The choice between driven and bored piles depends on the soil, the groundwater conditions and the availability of equipment: driven piles are preformed members that displace the soil and are quick to install, while bored piles are cast in holes drilled in the ground and cause no vibration, making them suitable in urban areas and near existing structures.

The capacity of a pile is determined by three methods: the static formula method, which computes the end bearing and skin friction from soil strength parameters; the dynamic formula method, which uses the resistance to driving measured by the number of blows; and the pile load test, which is the most reliable method and is performed on a trial pile before the main foundation is driven. This chapter explains the classification of piles, the static and dynamic capacity formulas, the concept of pile group efficiency, the phenomenon of negative skin friction, and worked numerical problems on pile capacity and group behaviour.

2. Types of Piles and Load Transfer

Piles are classified by the material used, by the method of installation and by the mode of load transfer. By material they are timber piles, precast concrete piles, cast-in-situ concrete piles, steel piles and composite piles. Timber piles are cheap but rot above the water table and have limited capacity, precast concrete piles are strong and durable but require careful handling and large driving equipment, cast-in-situ piles are formed in the ground and are economical because they are cut to the required length, steel piles are strong and can be driven to great depths, and composite piles combine two materials, such as a timber pile in a concrete shell, for special conditions.

By installation, piles are driven piles, which are hammered into the ground and displace the surrounding soil, increasing its density in the case of sands, and bored or cast-in-situ piles, which are formed by drilling a hole, placing reinforcement and filling it with concrete, without disturbing the soil significantly. By load transfer, piles are end-bearing piles, friction piles and combined piles. In addition, piles are used for special purposes: friction piles in very soft clay where the entire capacity comes from the shaft, compaction piles which densify loose granular soil by displacement, and under-reamed piles with enlarged bases which resist uplift in expansive soils.

Worked Example 1

A concrete pile of diameter 0.5 m is driven 12 m into a uniform clay having undrained cohesion of 45 kN/m2. Taking the adhesion factor as 0.6 and neglecting the base resistance, estimate the ultimate capacity of the pile.

Solution:

Perimeter of pile = pi x 0.5 = 1.571 m.

Side area = perimeter x length = 1.571 x 12 = 18.85 m2.

Skin friction capacity = adhesion factor x cohesion x side area = 0.6 x 45 x 18.85 = 509 kN.

Since base resistance is neglected, ultimate capacity = 509 kN.

Worked Example 2

For the pile of Worked Example 1, find the safe load with a factor of safety of 2.5.

Solution:

Safe load = ultimate capacity / factor of safety = 509 / 2.5 = 203.6 kN.

Therefore the safe load on the pile is about 204 kN.

3. Static and Dynamic Pile Capacity

In the static formula method, the ultimate capacity of a pile is the sum of the ultimate point resistance and the ultimate skin friction. The point resistance of a pile in clay is computed as the product of the undrained cohesion and a bearing capacity factor times the base area, while the skin friction in clay is the product of the adhesion factor, the cohesion and the side area. In sands, the point resistance is computed from the effective overburden pressure and a bearing capacity factor, while the skin friction depends on the lateral earth pressure coefficient, the angle of wall friction and the effective stress at the middle of each layer. The static method requires reliable values of the soil parameters and gives reasonable results when the soil profile is uniform.

The dynamic formula method estimates the capacity of a driven pile from the energy of the hammer and the penetration per blow. The well-known Engineering News formula relates the allowable load to the hammer energy, the final set, the height of fall and a constant that depends on the type of hammer. Dynamic formulas are simple and quick and are used on site for driving control, but they are approximate because they ignore the complex dynamic behaviour of the soil and the pile, and their results must be verified by a pile load test for important structures. The Hiley formula is a more refined dynamic formula that accounts for the temporary compression of the pile and the soil.

Worked Example 3

A pile is driven by a hammer whose energy per blow is 40 kN-m. The final set is 5 mm per blow and the constant for the hammer is 2.5 mm. Using the Engineering News relation that the allowable load equals the hammer energy per blow divided by (set plus constant), estimate the allowable load on the pile.

Solution:

Converting energy to kN-mm: 40 kN-m = 40000 kN-mm.

Set plus constant = 5 + 2.5 = 7.5 mm.

Allowable load = energy / (set + constant) = 40000 / 7.5 = 5333 kN.

Therefore the allowable load estimated by the Engineering News formula is about 5333 kN.

4. Pile Groups and Negative Skin Friction

Piles in a foundation are almost always installed in groups connected by a rigid pile cap, and the capacity of the group is not always equal to the sum of the individual pile capacities. The group efficiency is the ratio of the capacity of the group to the sum of the capacities of the individual piles, expressed as a percentage. In loose sand, a driven pile group acts like a single larger block and can have an efficiency greater than 100 percent because the driving densifies the sand, while in clay the group efficiency is usually less than 100 percent because the overlapping stress zones reduce the capacity. The group efficiency formulas depend on the number of piles, the spacing and the manner in which the group acts as a block.

Negative skin friction is the downward drag on a pile shaft caused by the settlement of the surrounding soil, which can happen when a fill is placed over soft clay, when the water table is lowered, or when the ground settles under adjacent loads. Negative skin friction adds an extra downward load to the pile that must be resisted by the pile, and it occurs over the upper part of the pile where the soil settles more than the pile, while positive skin friction acts over the lower part where the pile moves more than the soil. The neutral plane is the depth at which the relative movement between the pile and the soil is zero, separating the zone of negative friction above from the zone of positive friction below. The safe load on a pile must be reduced to account for the downdrag caused by negative skin friction.

Worked Example 4

A pile group consists of 9 piles, each with a safe capacity of 300 kN, arranged in a square grid. If the group efficiency is 0.8, determine the safe capacity of the group.

Solution:

Sum of individual capacities = 9 x 300 = 2700 kN.

Group capacity = group efficiency x sum of individual capacities = 0.8 x 2700 = 2160 kN.

Therefore the safe capacity of the pile group is 2160 kN.

Worked Example 5

If a negative skin friction force of 150 kN per pile acts on each pile of the group, find the reduced safe group capacity.

Solution:

Reduced safe capacity per pile = 300 - 150 = 150 kN.

Reduced group capacity = group efficiency x sum of reduced capacities = 0.8 x (9 x 150) = 0.8 x 1350 = 1080 kN.

Therefore the safe group capacity, allowing for negative skin friction, is 1080 kN.

5. Quick Revision Tables

Table 1: Classification of Piles

Basis Types
Material Timber, precast concrete, cast-in-situ, steel, composite
Installation Driven piles, bored / cast-in-situ piles
Load transfer End-bearing, friction, combined
Special use Compaction piles, under-reamed piles, tension piles

Table 2: Pile Capacity Concepts

Quantity Formula / Value Example
Skin friction in clay alpha x cu x perimeter x length 0.6 x 45 x 1.571 x 12 = 509 kN
Point resistance cu x Nc x base area Depends on soil
Ultimate capacity Point resistance + skin friction 509 kN
Safe load Ultimate / factor of safety 509/2.5 = 204 kN
Group efficiency Group capacity / sum of pile capacities 2160/2700 = 0.8
Negative skin friction Downdrag, reduces safe load 300 - 150 = 150 kN per pile

6. Mind Map

flowchart TD
    A[Pile Foundations] --> B[Classification]
    A --> C[Load transfer]
    A --> D[Capacity methods]
    A --> E[Group behaviour]
    B --> B1[Material: timber, concrete, steel]
    B --> B2[Installation: driven, bored]
    C --> C1[End bearing at tip]
    C --> C2[Friction along shaft]
    C --> C3[Combined]
    D --> D1[Static formula]
    D --> D2[Dynamic formula]
    D --> D3[Pile load test - most reliable]
    E --> E1[Group efficiency]
    E --> E2[Negative skin friction]
    E2 --> E3[Neutral plane separates zones]
    D1 --> F[Ultimate = point + skin]
    F --> G[Safe = ultimate / FOS]

7. Important Diagrams (SVG)

The following diagrams show the load transfer in a pile and the mechanism of negative skin friction.

Load Transfer in a Pile Ground PILE Pile cap + load P Positive skin friction (shaft resistance) TIP End bearing P = end bearing + skin friction Golden Rule Total pile load equals end bearing at the tip plus skin friction along the shaft.

Negative Skin Friction on a Pile Ground Fill settling down PILE Downward drag (negative friction) Neutral plane (no movement) Positive friction below Strong stratum Golden Rule Settling soil drags the pile down; reduce the safe pile load by the negative skin friction force.

8. Common Mistakes

  1. Many students compute the skin friction using the base area instead of the side area of the pile.
  2. A frequent error is to forget the adhesion factor in the clay skin friction formula, giving an overestimated capacity.
  3. Some candidates apply the group efficiency to the ultimate capacity and then divide by the factor of safety, double-counting the reduction.
  4. Students often assume the group efficiency is always 100 percent, ignoring that it is usually below 100 percent in clay.
  5. A common mistake is to ignore negative skin friction entirely, which leaves the pile design unsafe on settling ground.
  6. Many candidates confuse the neutral plane with the pile tip; the neutral plane is the depth where soil and pile move together.
  7. Some students use the set in millimetres but the energy in kN-m without converting units, giving a wrong dynamic formula result.
  8. A frequent error is to use a bored pile in loose sand where vibration-free installation is desired, and a driven pile where no vibration is permitted.

9. Exam Tips

  1. Memorise the skin friction formula for clay: alpha x cu x perimeter x length, and the point resistance concept for end-bearing piles.
  2. Learn the safe load equation: safe load = ultimate capacity / factor of safety, with the factor of safety typically 2.5 for piles.
  3. Remember that the group efficiency in clay is usually less than 1 while in loose sand it can exceed 1 because of densification.
  4. Note that the pile load test is the most reliable method of determining pile capacity.
  5. Understand negative skin friction: downward drag that must be subtracted from the safe load when the surrounding soil settles.
  6. Recall that bored piles cause less vibration and are preferred near existing structures.
  7. Practise the dynamic formula with consistent units of energy, set and constant.

10. Conclusion

Pile foundations are the most versatile and widely used of all deep foundations, and this chapter has covered their complete treatment. We have studied the classification of piles by material, installation and load transfer, the mechanisms of end bearing and skin friction, the static and dynamic methods of estimating pile capacity, and the verification of capacity by the pile load test. The worked examples have demonstrated the computation of skin friction in clay, the application of the factor of safety, the estimation of allowable load from the dynamic formula, the calculation of group efficiency and the reduction of capacity caused by negative skin friction. Pile design is an exercise in combining soil parameters with simple geometry, and these numerical skills are directly examinable. With a clear understanding of pile behaviour, the candidate is now ready to study well foundations, the massive deep foundation used under bridge piers, and to appreciate how the same principles of capacity and settlement apply to members of very different scale.