Subject: Civil Engineering Chapter: Foundation Engineering Topic: 19.10 Foundation Design
Foundation design is the process by which the engineer selects the type, size, depth and reinforcement of a foundation so that it safely transmits the structural loads to the soil while keeping settlements within acceptable limits and remaining economical to construct. The design procedure unites every topic studied in foundation engineering: the classification of foundations, the choice between shallow and deep types, the evaluation of the bearing capacity of the soil, the computation of settlement and the prevention of failure. For an examination candidate, foundation design is the ultimate test of the chapter because it requires the application of bearing capacity, settlement and structural strength checks in a logical sequence, and questions based on the design of isolated footings, combined footings and raft foundations appear in nearly every civil engineering paper.
The design of a foundation begins with the collection of data: the loads from the structure, the soil properties from the investigation report, the position of the water table and the permissible settlements. The first decision is whether a shallow foundation is feasible, which is tested by comparing the actual bearing pressure with the safe bearing capacity and the computed settlement with the permissible settlement. If a shallow foundation is feasible, the size of the footing is fixed by the safe bearing capacity, and the footing is then designed structurally to resist bending moment, one-way shear, punching shear and bearing on the soil. If the shallow foundation fails either the bearing or the settlement check, a deeper or a different foundation type is chosen.
The complete design of a footing involves three categories of checks: geotechnical checks, in which the bearing capacity and settlement are verified; structural checks, in which the thickness and reinforcement are fixed from bending and shear considerations; and constructability checks, which confirm that the footing can actually be built with the available equipment. This chapter explains the step-by-step procedure of foundation design, the determination of the footing size and thickness, the structural design of the footing in bending and shear, and the design of a pile cap and a raft foundation, together with worked numerical examples that illustrate each stage.
The design of a shallow foundation proceeds in a fixed sequence. In the first step, the total load on the foundation is determined, which is the sum of the column load, the self-weight of the footing and the weight of the soil above the footing, and this total load is used to find the required base area by dividing by the safe bearing capacity of the soil. In the second step, the width of the footing is fixed from the base area, rounding up to a convenient dimension, and the actual bearing pressure is computed and checked against the safe bearing capacity. In the third step, the thickness of the footing is determined from the punching shear and one-way shear requirements near the column, and the bending moment is computed at the face of the column to fix the reinforcement.
In the fourth step, the reinforcement is provided in two directions for a square or rectangular footing, with the main reinforcement placed along the length for a rectangular footing. The development length of the bars must be adequate so that the bars do not pull out from the column or the footing, and the cover and spacing must satisfy the code requirements. In the fifth step, the settlement of the footing is computed and compared with the permissible total and differential settlements. Finally, if any of these checks fails, the footing dimensions are revised, and the process is repeated until all the checks are satisfied. For a deep foundation, the same philosophy is followed, with the pile or well capacity evaluated instead of the bearing capacity of the shallow footing.
A column carries a service load of 900 kN. The safe bearing capacity of the soil is 180 kN/m2. Determine the size of a square footing, allowing for the self-weight of the footing and the soil above it as 10 percent of the column load.
Solution:
Total load = 1.1 x 900 = 990 kN.
Required base area = 990 / 180 = 5.5 m2.
Side of square footing = square root of 5.5 = 2.345 m.
Therefore a square footing of side 2.4 m is provided.
Check the actual bearing pressure for the footing of Worked Example 1.
Solution:
Base area provided = 2.4 x 2.4 = 5.76 m2.
Actual bearing pressure = 990 / 5.76 = 171.9 kN/m2.
Since 171.9 kN/m2 is less than 180 kN/m2, the footing is safe against bearing failure.
Once the base dimensions are fixed, the footing must be designed structurally so that it does not fail in bending or shear. The footing behaves like a slab resting on soil, with the upward soil pressure acting as the load and the column acting as a support. The maximum bending moment in a square footing occurs at the face of the column, and it is computed as the soil pressure times the projected area times the distance to the centroid of the projected area. The required depth of the footing is governed by this bending moment and by the shear requirements: one-way or beam shear is checked at a section at a distance equal to the effective depth from the face of the column, and two-way or punching shear is checked on a perimeter at a distance of half the effective depth from the column face.
The punching shear check is usually the governing criterion for the thickness of a footing, because the column punches through the footing along a truncated pyramid. The punching shear stress is computed as the shear force divided by the product of the perimeter and the effective depth, and it must not exceed the permissible punching shear stress of the concrete. The reinforcement is then provided in both directions at the bottom of the footing, with the area of steel computed from the bending moment and the lever arm, and the development length of the bars must be checked so that the bars are fully anchored in the footing.
For the square footing of side 2.4 m carrying a total load of 990 kN, the column is 400 mm square and the effective depth of the footing is 450 mm. Compute the punching shear force on the footing.
Solution:
Soil pressure q = 171.9 kN/m2.
The punching perimeter is at a distance d/2 = 0.225 m from the column face, giving a square of side 0.4 + 0.45 = 0.85 m.
Punching area (within the perimeter) = 0.85 x 0.85 = 0.7225 m2.
Load on punching area = q x punching area = 171.9 x 0.7225 = 124.2 kN.
Punching shear force = total load - load inside perimeter = 990 - 124.2 = 865.8 kN.
Punching perimeter = 4 x 0.85 = 3.4 m.
Punching shear stress = 865.8 / (3.4 x 0.45) = 565.9 kN/m2 = 0.566 MPa.
This stress is compared with the permissible punching shear stress to check the thickness.
Compute the maximum bending moment at the face of the column for the footing of Worked Example 3.
Solution:
Projection of the footing beyond the column face = (2.4 - 0.4) / 2 = 1.0 m.
Bending moment = q x width x projection2 / 2 = 171.9 x 2.4 x 1.0 x 1.0 / 2.
Bending moment = 171.9 x 1.2 = 206.3 kN-m per unit width of 2.4 m.
Therefore the design bending moment at the column face is 206.3 kN-m for the 2.4 m wide strip.
A pile cap is a thick reinforced concrete slab that connects a group of piles to the column and distributes the column load equally to all the piles. The design of a pile cap begins with the determination of the number of piles, which is the total load divided by the safe capacity of one pile, and the arrangement of the piles in a grid with a minimum spacing of about 2.5 to 3 times the pile diameter. The pile cap is then designed for bending along each direction, with the piles acting as supports and the column load acting downward, and the cap thickness is governed by the punching shear of the column and the one-way shear near the piles. The column load is assumed to be transferred to the piles by truss action, with the compression struts spreading from the column to each pile.
A raft foundation is designed as a large slab carrying all the columns of the structure, and it is ideal when the soil is weak and the footing would cover most of the plan area. In the simplest design, the raft is treated as an inverted floor slab, with the upward soil pressure acting as the load and the columns acting as supports, and the bending moments in the slab are computed for the column loads and the soil pressure. The thickness of the raft is governed by the bending moments and the shear, and the reinforcement is provided in both directions at the top and the bottom. The settlement of the raft is usually small and uniform because of its rigidity, which is precisely the advantage that makes it suitable for weak and compressible soils.
A column load of 1200 kN is to be carried on piles, each having a safe capacity of 300 kN. Determine the number of piles required.
Solution:
Number of piles = total load / safe capacity per pile = 1200 / 300 = 4 piles.
Therefore 4 piles are provided, arranged in a 2 x 2 grid.
If the piles are 400 mm in diameter, determine the minimum centre-to-centre spacing required.
Solution:
Minimum spacing = 3 x diameter = 3 x 0.4 = 1.2 m.
Therefore the piles are spaced at least 1.2 m centre to centre.
| Step | Action |
|---|---|
| 1 | Determine total load including self-weight |
| 2 | Fix base area = load / safe bearing capacity |
| 3 | Check actual bearing pressure |
| 4 | Fix thickness from punching and one-way shear |
| 5 | Compute bending moment at column face |
| 6 | Provide reinforcement and check development length |
| 7 | Check settlement |
| 8 | Revise if any check fails |
| Quantity | Formula | Example |
|---|---|---|
| Base area | A = Load / q safe | 990/180 = 5.5 m2 |
| Actual pressure | q = Load / A | 990/5.76 = 172 kN/m2 |
| Number of piles | N = Load / pile capacity | 1200/300 = 4 |
| Pile spacing | 3 x pile diameter | 3 x 0.4 = 1.2 m |
| Bending moment | q x B x projection2 / 2 | 171.9 x 2.4 x 1/2 = 206 kN-m |
| Punching shear stress | Shear / (perimeter x depth) | 865.8/(3.4 x 0.45) = 0.57 MPa |
flowchart TD
A[Foundation Design] --> B[Geotechnical checks]
A --> C[Structural checks]
A --> D[Constructability]
B --> B1[Bearing capacity check]
B --> B2[Settlement check]
C --> C1[Bending moment]
C --> C2[One-way shear]
C --> C3[Punching shear]
C --> C4[Reinforcement and development length]
D --> D1[Footing size and depth]
B1 --> E[A = load / safe capacity]
B2 --> E1[Total and differential limits]
C3 --> F[Governing for thickness]
C1 --> G[Moment at column face]
A --> H[Deep foundations]
H --> H1[Pile cap design]
H --> H2[Raft foundation]
The following diagrams show the components of a designed isolated footing and the pile cap arrangement.
Foundation design is the culmination of the entire study of foundation engineering, and this chapter has assembled every earlier topic into a single coherent procedure. We have followed the design of a shallow footing from the determination of the total load and the base area, through the bearing pressure check, the punching shear and bending moment computations, and the provision of reinforcement, and we have extended the same logic to the design of pile caps and raft foundations. The worked examples have demonstrated the sizing of a square footing, the punching shear stress calculation, the bending moment at the column face, the number of piles and their minimum spacing. The design process is a chain of checks, and the failure of any single check leads to a revision of the dimensions. A candidate who can carry out this procedure, from the load to the final footing dimensions, has mastered foundation engineering as a whole, because the same bearing capacity, settlement and structural strength concepts govern the behaviour of every foundation, whether shallow or deep. This completes the study of foundation engineering in the civil engineering syllabus.