1. Introduction

Secondary treatment is the biological stage of sewage treatment in which the dissolved and colloidal organic matter left after primary settling is removed by the action of micro-organisms. The primary settling tank removes only the settleable suspended solids and about 30 to 40 percent of the BOD, so the effluent still contains a large amount of organic matter which, if discharged, would consume the dissolved oxygen of the receiving stream. Secondary treatment is therefore the stage that gives the treatment plant its real pollution-removing power, and a well-designed secondary plant removes 85 to 95 percent of the BOD.

The principle of secondary treatment is to bring aerobic micro-organisms into intimate contact with the organic matter in the presence of oxygen, so that the micro-organisms use the organic matter as food and convert it into carbon dioxide, water and new cells. Two great families of processes achieve this: the suspended growth processes, in which the micro-organisms float freely in the liquid, and the attached growth processes, in which the micro-organisms grow as a slime on a fixed surface. The most important member of the suspended growth family is the activated sludge process, and the most important member of the attached growth family is the trickling filter.

In this chapter we will study the activated sludge process and the trickling filter in detail, together with the oxidation ponds and the septic tank which are used for smaller installations, and we will learn the design parameters of each process. Numerical problems on the organic loading of a trickling filter and on the sludge age of the activated sludge process are included, because such calculations are commonly set in examinations.

2. The Activated Sludge Process

The activated sludge process is the most widely used secondary treatment process for large towns. In this process the primary effluent is mixed with a culture of aerobic micro-organisms called activated sludge in an aeration tank, and air is supplied continuously, either by mechanical surface aerators or by compressed air through diffusers at the bottom of the tank. The mixture of the sewage and the micro-organisms, called the mixed liquor, is kept in suspension by the air, and the micro-organisms flocculate the organic matter and oxidise it.

After a detention period of about 4 to 8 hours in the aeration tank, the mixed liquor flows to a secondary settling tank, where the biological floc settles to the bottom as activated sludge. A portion of this settled sludge, called the return sludge, is pumped back to the aeration tank to maintain the necessary population of micro-organisms, and the remainder, called the waste sludge or excess sludge, is removed from the system and sent for sludge treatment. The clarified effluent overflows from the secondary tank and is chlorinated and disposed of.

The design of the activated sludge process is based on two important parameters. The first is the food to micro-organism ratio, abbreviated as F/M ratio, which is the ratio of the BOD applied per day to the mass of micro-organisms in the aeration tank; the F/M ratio for conventional plants is about 0.2 to 0.5 per day. The second is the sludge age or mean cell residence time, which is the average time that the micro-organisms remain in the system, defined as the ratio of the mass of micro-organisms in the aeration tank to the mass of micro-organisms removed per day in the waste sludge; the sludge age for a conventional plant is about 5 to 15 days.

The detention period of the aeration tank is about 4 to 8 hours, the volume of return sludge is about 20 to 30 percent of the sewage flow, and the concentration of the mixed liquor suspended solids, abbreviated as MLSS, is about 2000 to 3000 mg/l. The oxygen requirement of the process is about 1 kg of oxygen for each kilogram of BOD removed. A variant of the process, called the extended aeration process, uses a longer sludge age of about 20 to 30 days and produces less waste sludge, and it is used where no separate sludge treatment is desired.

3. The Trickling Filter

The trickling filter is an attached growth biological treatment unit in which the sewage is allowed to trickle down through a bed of coarse media while a slime of micro-organisms grows on the surface of the media. The media are broken stones, gravel, clinker or specially made plastic shapes, placed to a depth of about 1.8 to 3 m in a circular or rectangular tank with a perforated under-drainage system. The sewage is distributed over the top of the bed by rotating arms or by fixed distributors, and it trickles down over the slime in a thin film.

As the sewage trickles down, the micro-organisms of the slime absorb the organic matter and oxidise it, and air circulates through the void spaces of the bed, so the process is aerobic. The slime grows, and the outer layers of the slime die and are washed off by the flowing sewage; this is called sloughing, and the sloughed solids are removed in the secondary settling tank which follows the filter. The effluent of the trickling filter contains less than 30 mg/l of BOD when the filter is properly loaded, and the process is simpler to operate than the activated sludge process because it does not need the return of sludge.

The design of a trickling filter is based on the organic loading and the hydraulic loading. The organic loading is the BOD applied per unit volume of the filter bed per day, and it is expressed in kilograms of BOD per cubic metre per day, while the hydraulic loading is the volume of sewage applied per unit area of the bed per day. For a low rate trickling filter the organic loading is about 0.08 to 0.16 kg BOD per cubic metre per day and the BOD removal is about 80 to 90 percent, while for a high rate filter the organic loading is higher, up to about 1.0 kg BOD per cubic metre per day, but the removal efficiency is lower.

4. Oxidation Ponds and Septic Tanks

Oxidation ponds, also called waste stabilisation ponds or lagoons, are shallow basins in which sewage is stored for a long period, about 10 to 50 days, and stabilised by the combined action of bacteria and algae. The bacteria oxidise the organic matter and produce carbon dioxide and nutrients, while the algae, growing in the sunlight, use these products and produce the oxygen needed by the bacteria. The ponds are about 1 to 1.5 m deep, and they require a large land area, so they are used for small towns and for the treatment of sewage where land is cheap. The BOD removal in an oxidation pond can be as high as 80 to 90 percent.

The septic tank is the oldest and simplest device for the treatment of sewage from individual houses or small groups of buildings. It is a watertight tank in which the sewage is retained for about 24 hours, so that the settleable solids settle to the bottom, where they are decomposed anaerobically by the bacteria, and the grease floats to the surface and forms a scum which prevents the escape of gases. The clarified liquid overflows from the tank and is disposed of in a soak pit or a dispersion trench. The septic tank removes about 60 to 70 percent of the BOD, but its effluent is not fit for disposal in a stream and must be further treated in the soil.

The disposal of the septic tank effluent is done by subsoil irrigation, in which the effluent is led through open jointed pipes laid in dispersion trenches filled with gravel, from where it soaks into the soil and is purified by the soil bacteria. The soak pit is a covered pit filled with stones, into which the effluent is discharged to percolate into the surrounding soil. Both methods require a permeable soil and a low ground water table, and they must be located away from wells so that the ground water is not polluted.

Problem: A low rate trickling filter has a volume of 1200 cubic metres and receives a BOD load of 144 kg per day. Find the organic loading of the filter.

Solution: Organic loading = BOD applied / Volume of filter = 144/1200 = 0.12 kg BOD per cubic metre per day.

Answer: The organic loading is 0.12 kg BOD per cubic metre per day, which is within the range of 0.08 to 0.16 for a low rate filter.

Problem: The aeration tank of an activated sludge plant has a volume of 1000 cubic metres with a mixed liquor suspended solids concentration of 2500 mg/l. If the waste sludge removes 200 kg of suspended solids per day, find the sludge age of the system.

Solution: Mass of micro-organisms in the aeration tank = Volume x MLSS = 1000 x 2500 mg/l = 1000 cubic metres x 2500 g/cubic metre = 2,500,000 g = 2500 kg. Sludge age = Mass in aeration tank / Mass removed per day = 2500/200 = 12.5 days.

Answer: The sludge age is 12.5 days, which is a typical value for a conventional activated sludge plant.

Problem: A trickling filter of diameter 20 m receives 4 million litres of sewage per day. Find the hydraulic loading of the filter in litres per square metre per day.

Solution: Surface area = pi x D squared / 4 = 3.1416 x 400/4 = 314.16 square metres. Hydraulic loading = Flow / Area = 4,000,000/314.16 = 12,732 litres per square metre per day.

Answer: The hydraulic loading is about 12,730 litres per square metre per day.

5. Quick Revision Tables

Table 1: Activated Sludge Process Design Parameters

Parameter Conventional value
Aeration detention period 4 to 8 hours
MLSS concentration 2000 to 3000 mg/l
F/M ratio 0.2 to 0.5 per day
Sludge age 5 to 15 days
Return sludge 20 to 30 percent of flow
BOD removal 85 to 95 percent

Table 2: Trickling Filter Design Parameters

Parameter Low rate filter High rate filter
Organic loading (kg BOD/cu.m/day) 0.08 to 0.16 Up to 1.0
Hydraulic loading (l/sq.m/day) 3000 to 5000 10,000 to 30,000
BOD removal 80 to 90 percent 50 to 70 percent
Media depth 1.8 to 3 m 1 to 1.8 m
Sloughing Intermittent Continuous

6. Mind Map

flowchart TD
    A[Secondary Treatment] --> B[Activated sludge process]
    A --> C[Trickling filter]
    A --> D[Oxidation pond]
    A --> E[Septic tank]
    B --> B1[Aeration tank]
    B --> B2[Secondary settling tank]
    B --> B3[Return sludge]
    B --> B4[F/M ratio and sludge age]
    C --> C1[Media bed with slime]
    C --> C2[Rotating distributors]
    C --> C3[Low rate and high rate]
    D --> D1[Algae and bacteria]
    D --> D2[10 to 50 days detention]
    E --> E1[Anaerobic digestion in tank]
    E --> E2[Soak pit disposal]
    B1 --> F[MLSS 2000-3000 mg/l]
    C1 --> G[Organic loading 0.08-0.16]

7. Important Diagrams (SVG)

The following diagrams show the activated sludge process and the cross-section of a trickling filter.

Activated Sludge Process Primary effluent in Aeration tank air + mixed liquor Secondary tank sludge settles Return sludge to aeration tank Excess sludge wasted to sludge treatment E f f Golden Rule Return sludge keeps the micro-organisms in the aeration tank at the required density.

Cross-Section of a Trickling Filter Distributor arms Sewage spray Media bed broken stones with slime depth 1.8 to 3 m Under-drains Effluent outlet Air enters the void spaces Golden Rule The slime on the filter media oxidises the organic matter as sewage trickles past.

8. Common Mistakes

  1. Many students believe that the activated sludge process does not need any air; aeration is essential because the micro-organisms are aerobic.
  2. A frequent error is to forget the return sludge; without the return sludge the micro-organisms would be washed out of the aeration tank.
  3. Some candidates confuse the F/M ratio with the sludge age; the F/M ratio compares food to micro-organisms while the sludge age is the residence time of the micro-organisms.
  4. Students often think that the trickling filter is a mechanical filter; it is a biological unit in which a slime of micro-organisms grows on the media.
  5. A common mistake is to use the low rate filter loadings for a high rate filter; the high rate filter has a much higher organic and hydraulic loading.
  6. Many candidates forget that the septic tank works anaerobically and describe it as an aerobic process.
  7. Some students believe that the effluent of a septic tank can be discharged into a stream; it must be disposed of in the soil because it is still strong.
  8. Another recurring error is to ignore the oxygen requirement of the activated sludge process, which is about 1 kg of oxygen per kg of BOD removed.

9. Exam Tips

  1. Memorise the design parameters of the activated sludge process: aeration period of 4 to 8 hours, MLSS of 2000 to 3000 mg/l, F/M ratio of 0.2 to 0.5 and sludge age of 5 to 15 days.
  2. Remember the organic loading of a low rate trickling filter of 0.08 to 0.16 kg BOD per cubic metre per day and the BOD removal of 80 to 90 percent.
  3. Note that the secondary treatment removes 85 to 95 percent of the BOD overall.
  4. For the sludge age numerical, remember that sludge age = mass of micro-organisms in the aeration tank / mass removed per day.
  5. Remember that the return sludge is about 20 to 30 percent of the sewage flow.
  6. Note the detention period of the oxidation pond of 10 to 50 days and its depth of about 1 to 1.5 m.
  7. For the septic tank, remember the detention period of about 24 hours and the anaerobic decomposition of the settled sludge.
  8. In numerical problems on the trickling filter, use Organic loading = BOD applied per day / Volume of the filter, with units of kg per cubic metre per day.

10. Conclusion

Secondary treatment is the stage that actually destroys the organic pollution of the sewage, because it converts the dissolved and colloidal organic matter into stable products and new biomass through the action of micro-organisms. In this chapter we have studied the two principal processes, the activated sludge process and the trickling filter, together with their design parameters of aeration period, MLSS, F/M ratio, sludge age and organic loading, and we have examined the oxidation pond and the septic tank used for smaller installations. The numerical examples on the organic loading, the sludge age and the hydraulic loading have shown how the theoretical parameters are applied in design. A candidate who understands the difference between the suspended growth and attached growth processes, and who remembers the standard design values of each unit, will find this chapter one of the most predictable scoring areas of public health engineering, and will be ready to study the handling of the sludge that these biological processes produce.